									 43B Power Quality Analyzer 
									The Fluke 43B Power Quality Analyzer combines the most useful capabilities of a power quality analyzer, scope and multimeter in a single easy to use instrument.  The user interface is selectable in English, German, French, Italian and Spanish. 
								 | 
								
									   
								 | 
							
							
								| 
									 Voltage, current, and power harmonics 
									Up to 51st harmonic 
									Total harmonic distortion (THD) 
									Phase angle of individual harmonics 
									Continuously measure volts and amps on a cycle by cycle basis for up to 16 days 
									Use cursors to read time and date of sags and swells 
									One and three phase power on balanced loads 
									Watts, power factor, Cos, VA and VAR 
									Voltage and current waveforms 
								 | 
								
									 On screen graphics show you how to set up three phase power measurements 
									Battery life: Rechargeable Ni-Cd pack (charger included), 4 hrs typical (continuous) 
									Shock & Vibration: Mil 28800E, Type 3, class 111, Style B 
									Operating Temperature: 0oC to 50oC; Case: IP51 (dust, drip,waterproof) 
									Size (H x W x D): 232mm x 115mm x 50mm Weight: 1.1 kg 
									Safety: EN61010-1 CAT 111, 600V UL and CSA listed 
									Three Years Warranty 
								 | 
							
							
								| 
									 Technical Data 
									
										
											| 
												 Menu Items 
											 | 
											
												 Measurements 
											 | 
											
												 Ranges 
											 | 
											
												 Accuracy 
											 | 
										 
										
											| 
												 Volts/Amps/Hz 
											 | 
											
												 Volts 
												Amps 
												Mains Frequency 
												CF Crest Factor 
											 | 
											
												 5.000V  1250 V 
												50.00A  50.00 kA 
												40.0  70.0 Hz 
												1.0  10.0 
											 | 
											
												 - 
												± (1% + 10) 
												± (0.5% + 2) 
												± (5% +1) 
											 | 
										 
										
											| 
												 Power 
											 | 
											
												 Watts, VAR, VA, 
													PF, DPF, Cos j 
											 | 
											
												 250 W  1.56 GW 
												0.25  0.9 
												0.90  1.00 
											 | 
											
												 ± (4% + 4) 
												± 0.04 
												± 0.03 
											 | 
										 
										
											| 
												 Harmonics 
											 | 
											
												 Volts 
												Amps 
												Watts 
												K factor 
											 | 
											
												 1st to 51st harmonic 
												1st to 51st 
												1st to 51st 
												1.0 to 30.0 
											 | 
											
												 ± (3% + 2) to ±  (15% + 5) 
												± (3% + 8) to ±  (15% + 8) 
												± (5% + 2) to ±  (30% + 5) 
												± 10% 
											 | 
										 
										
											| 
												 Sags and swells 
											 | 
											
												 Voltage and Current 
											 | 
											
												 4 min  16 days selectable 
											 | 
											
												 ± (2% + 10) 
											 | 
										 
										
											| 
												 Transient Capture 
											 | 
											
												 40 ns pulse width 
												 
													Up to 40 transients 
											 | 
											
												 Select 20/50/100/200% 
												above or below line voltage 
											 | 
											
												 ± 5% of full scale 
											 | 
										 
										
											| 
												 Inrush Current 
											 | 
											
												 1 sec to 5 min selectable 
											 | 
											
												 1A to 1000A 
											 | 
											
												 ± 5% of full scale 
											 | 
										 
										
											| 
												 Ohms/Continuity 
												Capacitance 
											 | 
											
												 Ohms 
												Capacitance 
											 | 
											
												 500.0 W to 30.00 MW 
												50.00 nF to 500.0mF 
											 | 
											
												 ± (0.6% + 5) 
												± (2% + 10) 
											 | 
										 
										
											| 
												 Temperature 
													(with accessory) 
											 | 
											
												 °C 
												°F 
											 | 
											
												 -100.0°C to 400.0°C 
												-200.0°F to 800.0°F 
											 | 
											
												 ± (0.5% + 5) 
											 | 
										 
										
											| 
												 Scope 
											 | 
											
												 DC, AC, AC + DC, peak, 
													peak-peak, Hz, duty cycle, 
													phase, pulse width, crest factor 
											 | 
											
												 Sampling rate: 25 MS/sec 
												Bandwidth: 
													Voltage BW (Channel 1) 20 MHz 
													Current BW (Channel 2) 15 kHz 
											 | 
										 
										
											| 
												 Screen Saves 
											 | 
											
												 All functions 
											 | 
											
												 20 screens 
											 | 
										 
										
											| 
												 Recording 
											 | 
											
												 V/A/Hz, Power, 
													Harmonics, W/Cap, Temperature, Scope 
											 | 
											
												 4 min- 16 days selectable 
											 | 
											
												 Select any two parameters in each display mode 
											 | 
										 
									 
									
								 |